Omron CQM1H-CLK21 Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para Hardware Omron CQM1H-CLK21. Omron CQM1H-CLK21 User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 401
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes

Resumo do Conteúdo

Página 1 - Controller Link Units

OPERATION MANUALCat. No. W309-E1-09SYSMACCS1W-CLK21-V1CJ1W-CLK21-V1C200HW-CLK21CVM1-CLK21CQM1H-CLK21(CS1W-RPT01/02/03 Repeater Units)Controller Link U

Página 2

xiTABLE OF CONTENTSSECTION 10Adding Nodes and Editing Active Data Link Tables . . . . . 33110-1 Adding Nodes Using a Repeater Unit. . . . . . . . . .

Página 3

77Wiring Section 3-3Remove the covers from the tips of the cables’ ST connectors if there arecovers protecting the ST connectors.Note To replace the O

Página 4 - Visual Aids

78Constructing Networks with Repeater Units Section 3-4Note Lf is fiber length in km, Ta is ambient temperature, and λ is the peak wave-length of the

Página 5 - Unit Versions

79Constructing Networks with Repeater Units Section 3-4Units/Support Boards or Repeater Units) at both ends of each networksegment created by installi

Página 6 - Unit Version Notation

80Constructing Networks with Repeater Units Section 3-43-4-2 Number of Repeater UnitsThe number of Repeater Units that can be connected in a Wired Con

Página 7

81Constructing Networks with Repeater Units Section 3-4Long-distance Wiring: 2-stage Repeater Unit ConnectionNot more than 2 Repeater Units (2 stages)

Página 8

82Constructing Networks with Repeater Units Section 3-4The path from one node to another travels via three Repeater Units(3 stages). This kind of netw

Página 9

83Constructing Networks with Repeater Units Section 3-4Partial Conversion to Optical FiberCombining T-Branch Wiring (2-stage Repeater) and Partial Opt

Página 10 - TABLE OF CONTENTS

84Constructing Networks with Repeater Units Section 3-4

Página 11

85SECTION 4Preparations for CommunicationsThis section describes the settings required for starting communications. These basic settings are required

Página 12 - About this Manual:

86CS-series Controller Link Units Section 4-14-1 CS-series Controller Link UnitsThe following settings are required for a Controller Link Unit used wi

Página 13

xiiTABLE OF CONTENTS

Página 14 - LIMITATIONS OF LIABILITY

87CS-series Controller Link Units Section 4-1Set the node address using a small flat-blade screwdriver, being careful not todamage the rotary switches

Página 15 - Application Considerations

88CS-series Controller Link Units Section 4-1ther communications will stop, or the INS indicator will not light and you willbe unable to participate i

Página 16 - Disclaimers

89CJ-series Controller Link Units Section 4-22. The default setting is 2 Mbps, 500 m.4-1-5 Terminating ResistanceTurn ON the terminating resistance us

Página 17

90CJ-series Controller Link Units Section 4-24-2-1 OverviewUnit NumberNode AddressBaud RateNote Factory default setting is in bold.Terminating Resista

Página 18 - PRECAUTIONS

91CJ-series Controller Link Units Section 4-25. The default setting is “0.”6. The unit number determines the words used by the Controller Link Unit in

Página 19 - 3 Safety Precautions

92CJ-series Controller Link Units Section 4-26. Only node addresses 1 through 32 can be used on networks for which 62nodes have not been enabled.7. Th

Página 20

93C200HX/HG/HE Controller Link Units Section 4-3Note 1. Always turn OFF the PLC’s power before setting the terminating resistanceswitch.2. Turn ON the

Página 21 - 5 Applications Precautions

94C200HX/HG/HE Controller Link Units Section 4-34-3-1 OverviewNode AddressBaud Rate and Operating Level•Baud RateNote Factory default setting is in bo

Página 22 - Applications Precautions 5

95C200HX/HG/HE Controller Link Units Section 4-3Set the node address using a small flat-blade screwdriver, being careful not todamage the rotary switc

Página 23

96C200HX/HG/HE Controller Link Units Section 4-3Note 1. Do not use the same operating level for more than one Unit mounted to thesame PLC. An error wi

Página 24 - SECTION 1

xiiiAbout this Manual:This manual describes the installation, setup, and operation of the C200HW-CLK21, CS1W-CLK21-V1, CJ1W-CLK21-V1, CVM1-CLK21, and

Página 25 - 1-1 Overview

97CVM1 and CV-series Controller Link Units Section 4-44-4 CVM1 and CV-series Controller Link UnitsThe following settings are required for a Controller

Página 26 - Overview Section 1-1

98CVM1 and CV-series Controller Link Units Section 4-44-4-2 Unit NumberSet the unit number for each Unit using the rotary switches on the front of the

Página 27

99CVM1 and CV-series Controller Link Units Section 4-42. Do not set the same node address twice within the same Network. An errorwill occur if the sam

Página 28

100CQM1H-series Controller Link Units Section 4-5Note 1. Always turn OFF the PLC’s power before setting the terminating resistanceswitch.2. Turn ON th

Página 29

101CQM1H-series Controller Link Units Section 4-54-5-2 Node AddressesSet the node address of each Unit in the Network using the rotary switch onthe fr

Página 30

102Repeater Units Section 4-6Note Set the same baud rate for all the nodes on the Network. Normal communica-tion cannot be performed unless the same b

Página 31 - 1-1-2 Features

103Repeater Units Section 4-64-6-1 Wire-to-Wire Repeater Unit Terminating Resistance Switch for SL1Note The factory default setting is in bold.Termina

Página 32

104Repeater Units Section 4-6See pages 15 and 79 for details on the maximum transmission distance.Note 1. Always turn OFF power to the Repeater Unit b

Página 33

105SECTION 5Data LinksThis section describes how to use data links in a Controller Link Network. Refer to SECTION 2 Basic Procedures for anoutline of

Página 34 - 1-2-1 System Configuration

106What Are Data Links? Section 5-15-1 What Are Data Links?Data links automatically exchange data in the preset areas between nodes(PLCs and/or comput

Página 35 - Long-distance Wiring

xivSection 7 describes the method used to connect multiple networks through CS/CJ-series, CVM1, andCV-series PLCs. The section also describes remote p

Página 36 - 1-2-2 General Specifications

107What Are Data Links? Section 5-1Manually set data links are used to create flexible data links that meet theneeds of the individual system.• Data l

Página 37

108What Are Data Links? Section 5-1Automatically Setting Data Links with Equality LayoutAutomatic setting can be used to create simple data links.• Us

Página 38

109What Are Data Links? Section 5-1• There are three types of 1:N allocations.• Programming Devices (including Programming Consoles) are used to setth

Página 39 - Wired System

110What Are Data Links? Section 5-1Using OffsetsFor automatically set data links, all of the send words transmitted by a nodeare received by other nod

Página 40

111What Are Data Links? Section 5-1Note The following table shows the status of the data link refresh area when a noderegistered in the data link tabl

Página 41 - Controller Link Unit Models

112What Are Data Links? Section 5-15-1-2 Differences between Manual and Automatic SettingNote a) The following are true for computer nodes (i.e., comp

Página 42 - 1-2-5 Devices for Connection

113Setting Data Links Section 5-25-2 Setting Data Links5-2-1 Selecting Manual or Automatic SettingSpecify either the manual or automatic data link mod

Página 43 - Relay Terminal Blocks

114Setting Data Links Section 5-2Note 1. Be sure to set the bit in the DM Area’s (CPU Bus Unit Area’s) softwareswitches (DM30000 + 100 × unit number)

Página 44 - 1-2-6 Programming Devices

115Setting Data Links Section 5-24. When using the Controller Link Support Software to set a CJ-series Con-troller Link Unit, use one of the following

Página 45

116Setting Data Links Section 5-2First data link sta-tus wordSet the first word to store data link status. An area of 16 words is used.CIO Area: CIO

Página 46

xvRead and Understand this ManualPlease read and understand this manual before using the product. Please consult your OMRON representative if you have

Página 47

117Setting Data Links Section 5-2Note a) The total number of words in data link send and receive areasmust not exceed 20,000 per node when using Contr

Página 48

118Setting Data Links Section 5-2Note a) The total number of words in data link send and receive areasmust not exceed 8,000 per node.b) The following

Página 49 - 1-4 Basic Procedures

119Setting Data Links Section 5-2CVM1 and CV-series PLCsSetting item Setting rangePLC model Set the model of the PLC’s CPU Unit.Nodes 1 to 32Set the a

Página 50 - 1-5 Application Precautions

120Setting Data Links Section 5-2Note a) The total number of words in data link send and receive areasmust not exceed 8,000 per node.b) The following

Página 51

121Setting Data Links Section 5-2Note a) The total number of words in data link send and receive areasmust not exceed 8,000 per node.b) The following

Página 52

122Setting Data Links Section 5-2(Data link start word – 1) + Total number of send/receive words in area ≤247 (IR Area)63 (LR Area)5999 (DM Area)6143

Página 53

123Setting Data Links Section 5-25-2-3 Manual Setting ExamplesThis section shows examples of manually creating data link tables on theController Link

Página 54 - Basic Procedures

124Setting Data Links Section 5-2Checking the Data Link TablesTransferring the Data Link TablesSaving the Data Link Tables

Página 55 - 2-1 Data Links Procedures

125Setting Data Links Section 5-2SAMPLE2.CLK: Different Allocations to Each NodeData links can be created so that one node does not receive from all o

Página 56

126Setting Data Links Section 5-2Data Link TablesSAMPLE3.CLK: Creating Data Link Groups within a NetworkA data links consisting of multiple groups wit

Página 57

xviApplication ConsiderationsSUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to

Página 58 - 6. Set the data link mode

127Setting Data Links Section 5-2Device Information SettingData Link Tables

Página 59

128Setting Data Links Section 5-2SAMPLE4.CLK: Receiving Only Part of Send Data and OffsetsOnly area 2 is used in this example.Note A Controller Link S

Página 60 - Common Type

129Setting Data Links Section 5-2Data Link Tables5-2-4 Automatic SettingData links can be automatically created by setting values in the DM ParameterA

Página 61 - 1 to 1 Type

130Setting Data Links Section 5-2CS/CJ-series Startup NodeAutomatic setting for the CS/CJ Series can be performed using either equalitylayout (previou

Página 62

131Setting Data Links Section 5-2Automatic Setting, 1:N AllocationsThis method is used to simplify the establishment of 1:N allocation data linksbetwe

Página 63 - 2-2 Message Service Procedure

132Setting Data Links Section 5-2Set the following parameter in the DM Parameter Area of the PLC at the star-tup node.Automatic Setting, Equality Layo

Página 64

133Setting Data Links Section 5-2Note a) The total number of words in data link send and receive areasmust not exceed 20,000 per node when using Contr

Página 65

134Setting Data Links Section 5-21:N Allocation, Common TypeFeatures of Common Type 1:N Allocation• Data communications are 1:1 between the master nod

Página 66 - Installation and Wiring

135Setting Data Links Section 5-2Words N+22 through N+25 register nodes that will participate in the datalinks. The numbers shown in the table are the

Página 67

136Setting Data Links Section 5-2Note 1. Node 1 is the master node. Node 1 must be registered as a participatingnode.2. The startup node (the node tha

Página 68

xviiDisclaimersCHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons.It i

Página 69 - Dimensions (Unit: mm)

137Setting Data Links Section 5-23. When using area 2 only, set the area for area 1 and the number of sendwords for area 1 to 0.4. When using area 1 o

Página 70

138Setting Data Links Section 5-21:N Allocations, 1 to 1 TypeFeatures of 1 to 1 Type 1:N Allocation• Data communications are 1:1 between the master no

Página 71 - ERH M/A LNK RD

139Setting Data Links Section 5-2Words N+22 through N+25 register nodes that will participate in the datalinks. The numbers in the table are the node

Página 72 - Wired Unit Indicators

140Setting Data Links Section 5-2Note 1. Node 1 becomes the master node. Node 1 must be registered as a partic-ipating node.2. Only one area can be sp

Página 73 - Name Color Status Meaning

141Setting Data Links Section 5-2(Area start word − 1) + (Total number of send and receive words ofmaster node *)≤ 6143 (when using the IR or CIO Area

Página 74

142Setting Data Links Section 5-2• Each slave nodes receives data from the previous node and then sendsdata to the next node. Data is thus passed in a

Página 75

143Setting Data Links Section 5-2Note 1. Node 1 becomes the master node. Node 1 must be registered as a partic-ipating node.2. Only one area can be sp

Página 76

144Setting Data Links Section 5-2Total number of words in data link send and receive areas of masternode =Number of common send words in master node +

Página 77 - CS1W-RPT01

145Setting Data Links Section 5-211. If the LR Area in the C200HX/HG/HE or CQM1H-series PLC is automati-cally set for a data link with a CVM1, CV-seri

Página 78 - Repeater Unit Indicators

146Setting Data Links Section 5-2Note a) The total number of words in data link send and receive areasmust not exceed 8,000 per node.b) The following

Página 80 - CS1W-RPT03

147Setting Data Links Section 5-2CVM1 or CV-series Startup NodeSet the following DM Parameter Area of the PLC of the startup node.SettingsData link mo

Página 81 - 3-2 Unit Installation

148Setting Data Links Section 5-2Note a) The total number of words in data link send and receive areasmust not exceed 8,000 per node.b) The following

Página 82 - Unit Installation Section 3-2

149Setting Data Links Section 5-22. If the LR Area in a C200HX/HG/HE or CQM1H-series PLC is manually setfor a data link with a CVM1, CV-series, or CS/

Página 83

150Setting Data Links Section 5-2CQM1H-series Startup NodeSet the following DM Parameter Area of the PLC of the startup node.SettingsData link mode Se

Página 84

151Setting Data Links Section 5-2Note a) The total number of words in data link send and receive areasmust not exceed 8,000 per node.b) The following

Página 85

152Setting Data Links Section 5-2Data Link Areas CreatedDM Parameter Setting Example for 1:N Allocation, Common TypeWhen automatic data link creation

Página 86

153Starting and Stopping Data Links Section 5-3Data Link AreasNote 1. Node 1 is the master node.2. The startup node (the node that sets the above DM p

Página 87

154Starting and Stopping Data Links Section 5-35-3-1 Using a Programming Device or the User ProgramSet the software switch (AR or DM Start Bit) in the

Página 88

155Starting and Stopping Data Links Section 5-3CVM1 and CV-series Start BitCQM1H-series Start Bit5-3-2 Using the Controller Link Support Software and

Página 89 - 3-3 Wiring

156Checking Data Link Status Section 5-4Issuing the FINS Command from CVM1, CV-series, CS/CJ-series, and CQM1H-series PLCsData links can be stopped by

Página 90

xixPRECAUTIONSThis section provides general precautions for using the Controller Link Unit and related devices.The information contained in this secti

Página 91

157Checking Data Link Status Section 5-4When 8-bit Format is Specified (i.e., when using a C200HX/HG/HE, CVM1, CV-series, or CQM1H-series PLC or when

Página 92 - Approx. 40 mm

158Checking Data Link Status Section 5-45. The following shows an example of an insufficient (short) receive area.6. The following shows an example of

Página 93 - 25 mm max

159Checking Data Link Status Section 5-45. With CS/CJ-series PLCs, the status of the words from first status word +16 to first status word + 30 when 8

Página 94 - 3-3-2 Repeater Units

160Checking Data Link Status Section 5-4The data link status storage area is set as follows:Note a) N: Unit numberb) Only status for nodes 1 to 6 are

Página 95

161Checking Data Link Status Section 5-4Note The data link storage format setting is enabled with the data link startup nodesetting. Therefore, if mul

Página 96

162Checking Data Link Status Section 5-45-4-5 Error Detection Program ExampleWhen the source node's data link is participating, the AND condition

Página 97 - S3200-H@@@@@@@

163Checking Data Link Status Section 5-4Processing Data Only when Operation Is Normal Using the IL-ILC and JMP-JME InstructionsPerform processing only

Página 98

164Checking Data Link Status Section 5-4quently cleared to 0000. Data processing methods that will not processdata or arithmetic operations when error

Página 99

165SECTION 6Message ServiceThis section explains how to use the message service provided by a Controller Link Unit. It also explains the FINScommands

Página 100 - Wiring Section 3-3

166Introduction Section 6-16-1 IntroductionA message service is a command/response system used for data transmis-sion between nodes on a network, i.e.

Página 101

xxIntended Audience 11 Intended AudienceThis manual is intended for the following personnel, who must also haveknowledge of electrical systems (an ele

Página 102 - 3-4-1 Segments

167Introduction Section 6-16-1-1 SEND and RECVI/O memory data from other nodes can be read or written by simply using theprogram in the CPU Unit of a

Página 103

168Introduction Section 6-12. With the message service, there is no guarantee that a message to a des-tination node will reach its destination. It is

Página 104

169Introduction Section 6-1C200HX/HG/HE PLCsSEND SEND transmits “n” words beginning with S (the beginning source word fordata transmission at the sour

Página 105 - 3-4-3 Terminating Resistance

170Introduction Section 6-1RECV RECV receives “m” words beginning with S (the beginning word for datatransmission at the destination node, M) to the w

Página 106 - Segment 2

171Introduction Section 6-1sage may be lost in transit due to noise or some other condition. Whenusing the message service, it is advisable to prevent

Página 107

172Introduction Section 6-1Note Specify the area code according to the following table.Note 1. Words 0 to 2555 in the IR Area can send and receive dat

Página 108 - SECTION 4

173Introduction Section 6-1CVM1 and CV-series PLCsSEND SEND transmits “n” words beginning with S (the beginning word for datatransmission at the sourc

Página 109 - CLK21-V1

174Introduction Section 6-1RECV RECV receives “m” words beginning with S (the beginning word for datatransmission at the destination node, M) to the w

Página 110 - 4-1-3 Node Addresses

175Introduction Section 6-1CQM1H-series PLCsSEND SEND transmits “n” words beginning with S (the beginning word for datatransmission at the source node

Página 111 - 4-1-4 Baud Rates

176Introduction Section 6-1RECV RECV receives “m” words beginning with S (the beginning word for datatransmission at the destination node, M) to the w

Página 112 - 4-1-5 Terminating Resistance

CS1W-CLK21-V1CJ1W-CLK21-V1C200HW-CLK21CVM1-CLK21CQM1H-CLK21(CS1W-RPT01/02/03 Repeater Units)Controller Link UnitsOperation ManualRevised January 2006

Página 113 - 4-2-2 Unit Number

xxiOperating Environment Precautions 4• The PLC will turn OFF all outputs when its self-diagnosis function detectsany error or when a severe failure a

Página 114 - 4-2-3 Node Addresses

177Introduction Section 6-1using the message service, it is advisable to prevent this situation from oc-curring by performing resend processing at the

Página 115 - 4-2-5 Terminating Resistance

178Introduction Section 6-1Note Specify the area code according to the following table.Note 1. Words 0 to 2555 in the IR Area can send and receive dat

Página 116

179Introduction Section 6-16-1-2 CMND (CVM1, CV-series, CS/CJ-series, and CQM1H-series PLCs Only)The CMND instruction can be executed in the user prog

Página 117 - 4-3-2 Node Addresses

180Introduction Section 6-1sage service, it is advisable to prevent this situation from occurring by per-forming resend processing at the node where i

Página 118 - Pins 1, 2: Baud rate

181Introduction Section 6-1“00” as the local network address in the routing tables, and then specifythat number.2. With the message service, there is

Página 119 - 4-3-4 Terminating Resistance

182Introduction Section 6-1CQM1H-series PLCs CMND sends “n” bytes of command data beginning with S (the beginningword for storing command data at the

Página 120 - 4-4-1 Overview

183Introduction Section 6-1curring by performing resend processing at the node where instructionsare issued. With the SEND, RECV, and CMND instruction

Página 121 - 4-4-3 Node Addresses

184Introduction Section 6-1For details on commands for CS/CJ-series PLCs, refer to the CS/CJ-seriesProgrammable Controllers Instructions Reference Man

Página 122 - 4-4-5 Terminating Resistance

185Introduction Section 6-1C200HX/HG/HE PLCsNote 1. Words in the Internal Relay Area 1 (IR 000 to IR 235) and Special RelayArea 1 (SR 236 to SR 255) a

Página 123 - 4-5-1 Overview

186Selecting Communications Instructions Section 6-2Note 1. SR 253 to SR 255 cannot be written at the source node, even if they arespecified by the RE

Página 124 - 4-5-3 Baud Rates

xxiiApplications Precautions 55 Applications PrecautionsObserve the following precautions when using the Controller Link Unit.!WARNING Failure to abid

Página 125 - 4-6 Repeater Units

187Selecting Communications Instructions Section 6-26-2-1 Message Service OperationsNote 1. CMND cannot be used with C200HX/HG/HE PLCs.2. If a compute

Página 126 - Wire-to-Optical

188Selecting Communications Instructions Section 6-26-2-2 Message Service SpecificationsItem SpecificationsTransmission format C200HX/HG/HE PLCs1:1 SE

Página 127 - 4-6-3 Terminating Resistance

189Using the Message Service Section 6-36-3 Using the Message ServiceWith SEND, RECV, and CMND, the Network Instruction Enabled Flag andNetwork Instru

Página 128 - Data Links

190Using the Message Service Section 6-3C200HX/HG/HE PLCsCVM1, and CV-series PLCsCQM1H-series PLCsNetwork StatusThe nodes on the network are shown in

Página 129 - 5-1 What Are Data Links?

191Using the Message Service Section 6-3SEND/RECV Flag Operations• The Network Instruction Enabled Flag turns OFF during transmission orreception, and

Página 130

192Using the Message Service Section 6-3C200HX/HG/HE and CQM1H-series PLC Response CodesThe results of executing SEND and RECV instructions are reflec

Página 131 - Node#1 Node#2 Node#3

193Using the Message Service Section 6-3Simultaneous Execution of Communications InstructionsC200HX/HG/HE PLCs CS/CJ-series, CVM1, and CV-series PLCsO

Página 132 - 3G8F7-CLK21-V1 (for PCI bus)

194Using the Message Service Section 6-3PLC Programming ExamplesCS/CJ-series PLCsDIFU(13) 120001120000 A20207@MOV(21) #000A D00000120000RSKEEP 1

Página 133 - Using Offsets

195Using the Message Service Section 6-3Note 1. With CS/CJ-series PLCs, the Network Instruction Enabled Flag in A20200to A20207 corresponding to commu

Página 134 - Send data of node 1

196Using the Message Service Section 6-3C200HX/HG/HE PLCsDIFU(13) 3100131000 25204@XFER(70) #0010 000 DM 0010@MOV(21) #000A DM 000031000RS

Página 135

xxiiiApplications Precautions 5• Double-check all wiring and switch settings before turning ON the powersupply. Incorrect wiring may result in burning

Página 136 - 5-2 Setting Data Links

197Using the Message Service Section 6-3Note When using the sample program, make sure that the bits and words used inthe sample program are not the sa

Página 137 - 5-2-2 Manual Setting

198Using the Message Service Section 6-3CVM1 and CV-series PLCsNote When using the sample program, make sure that the bits and words used inthe sample

Página 138

199FINS Commands and Responses Section 6-46-4 FINS Commands and Responses6-4-1 FINS Communications ServiceThe FINS communications service is a communi

Página 139 - LR 00 to LR 199 (*)

200FINS Commands and Responses Section 6-4Command Codes The command code consists of two bytes of data, and indicates the contentsof the command. A FI

Página 140 - ≤ 6143 (CIO Area)

201Commands and Responses for Controller Link Units Section 6-56-5 Commands and Responses for Controller Link Units6-5-1 Command Codes6-5-2 DATA LINK

Página 141

202Commands and Responses for Controller Link Units Section 6-5Response BlockThe DATA LINK STOP command can be received only while the data links area

Página 142 - CVM1 and CV-series PLCs

203Commands and Responses for Controller Link Units Section 6-5tions Controller version number, and the third represents the Unit versionnumber.Wired/

Página 143 - ≤ 2555 (CIO Area)

204Commands and Responses for Controller Link Units Section 6-5Status 2 (response): For C200HX/HG/HE, CVM1, and CV-series ControllerLink Units, always

Página 144

205Commands and Responses for Controller Link Units Section 6-5Network participation status (response): The following diagram shows thebits correspond

Página 145 - ≤247 (IR Area)

206Commands and Responses for Controller Link Units Section 6-5ON, the network participation status of nodes 33 to 62 is returned in the upperfour bit

Página 146 - 5-2-3 Manual Setting Examples

xxivConformance to EC Directives 66 Conformance to EC DirectivesThe Controller Link Units conform to EMC and Low Voltage Directives as fol-lows:EMC Di

Página 147 - Saving the Data Link Tables

207Commands and Responses for Controller Link Units Section 6-5Data link data error counter (response): The total number of data link datareception er

Página 148

208Commands and Responses for Controller Link Units Section 6-5Status flag (response): The overall data link status is returned in one byte ofdata, as

Página 149 - Data Link Area Structure

209Commands and Responses for Controller Link Units Section 6-54. Any node which is not active in the network retains the status that existedimmediate

Página 150 - Device Information Setting

210Commands and Responses for Controller Link Units Section 6-56-5-10 BROADCAST TEST DATA SENDBroadcasts test data to all nodes in a specified network

Página 151

211Commands and Responses for Controller Link Units Section 6-5The configuration of each error record is as follows:Error code, details: These paramet

Página 152 - 5-2-4 Automatic Setting

212Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-66-6 Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs6-6-1 Com

Página 153 - CS/CJ-series Startup Node

213Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-6Note The meanings of the memory area codes for the Expansion DM area aresh

Página 154

214Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-6Data Configuration The configuration of the various types of data that can

Página 155

215Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-6Memory AreasThe following areas can be read. (Refer to 6-6-2 Memory Area D

Página 156

216Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-66-6-5 MULTIPLE MEMORY AREA READReads the contents of the specified number

Página 157

1SECTION 1Features and System ConfigurationThis section provides basic information on Controller Link Networks, and will give the reader an overview o

Página 158

217Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-6Response BlockParameters Program no. (command and response): Set to 0000 (

Página 159

218Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-6No. of bytes (command and response): The command specifies the num-ber of

Página 160

219Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-6Response Block6-6-10 CONTROLLER DATA READReads the following data:• Contro

Página 161

220Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-66-6-11 CONTROLLER STATUS READReads the status of the Controller.Command Bl

Página 162

221Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-6FAL/FALS No. (response): The number of the highest priority FAL/FALSerror

Página 163 - × Number of slave

222Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-6Parameters Year, month, date, hour, minute, second, day (command): Each sp

Página 164

223Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-6Command BlockResponse BlockParameters No. of bits/flags (command): The num

Página 165 - Item Setting range

224Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs Section 6-6Response BlockNote The bits (flags) in the following memory areas can be f

Página 166

225Response Codes Section 6-7IR, SR, LR, HR, and AR Areas:Timers/Counters: Status of the Completion Flag will be returned as fol-lows:00 (Hex): No for

Página 167 - × Number of nodes

226Response Codes Section 6-76-7-2 Network Relay ErrorsA network relay error will occur whenever a command cannot reach the desti-nation. These errors

Página 168 - C200HX/HG/HE Startup Node

2Overview Section 1-11-1 Overview1-1-1 What Is the Controller Link?The Controller Link is an FA network that can send and receive large datapackets fl

Página 169

227Response Codes Section 6-7Example 1 In this example, data cannot be transferred between Controller Link Units dueto some cause such as a routing ta

Página 170 - (EM must be installed)

228Response Codes Section 6-701: Local node error 01 Local node not part of Network Add to Network.02 Token time-out, node address too large Set the l

Página 171

229Response Codes Section 6-705: Routing error 01 Destination node address is not set in the routing table.Set the destination node address in the rou

Página 172

230Response Codes Section 6-720: Read not possible 02 The data is protected. Execute the instruction again after issuing the PROGRAM AREA PROTECT CLEA

Página 173 - CQM1H-series Startup Node

231Response Codes Section 6-722: Not executable in cur-rent mode01 The mode is wrong (executing). Check the operating mode.Data links are active. Chec

Página 174 - ≤ 247 (IR Area)

232Response Codes Section 6-726: Command error 01 The specified area is not protected. This response code will be returned if an attempt is made to cl

Página 175

233SECTION 7Network InterconnectionsThis section describes the method used to connect multiple networks through CS/CJ-series, CVM1, and CV-series PLCs

Página 176 - •Automatically Set Data Links

234What is Network Interconnection? Section 7-17-1 What is Network Interconnection?Network interconnection enables commands and responses for the mess

Página 177

235What is Network Interconnection? Section 7-1• Although a C200HX/HG/HE PLC supports multiple (maximum of 2) Com-munications Units, it cannot functio

Página 178 - 5-3-3 Using FINS Commands

236Remote Programming and Monitoring Section 7-27-2 Remote Programming and MonitoringA remote PLC can be programmed and monitored across a network fro

Página 179

3Overview Section 1-1Connecting Repeater Units Using Twisted-pair Cable (Wired Units)T-Branch WiringLong-distance WiringConverting Part of the Transmi

Página 180 - 0: Normal

237Remote Programming and Monitoring Section 7-2CX-ProgrammerA CX-Programmer connected to a CS/CJ-series, C200HX/HG/HE, CVM1,CV-series, or CQM1H CPU U

Página 181

238Remote Programming and Monitoring Section 7-2CX-ProgrammerA CX-Programmer connected to a CS/CJ-series, C200HX/HG/HE, CVM1,CV-series, or CQM1H-serie

Página 182 - × unit number + 6

239Routing Tables Section 7-3CX-ProgrammerA CX-Programmer connected to a CS/CJ-series, C200HX/HG/HE, CVM1,CV-series, or CQM1H-series CPU Unit can prog

Página 183

240Setting Routing Tables Section 7-42. The network address is the address of the network connected to the Unit(between 1 and 127). The address is set

Página 184 - 5-4-3 Data Link Status Area

241Setting Routing Tables Section 7-44. When using a CVM1 or CV-series CPU Unit manufactured prior to April1996, be sure to register routing tables wh

Página 185

242Setting Routing Tables Section 7-4SIOU Unit No.:Unit number of the Communications Unit (operating level for C200HX/HG/HEPLCs; always 0 for CQM1H-se

Página 186

243Setting Routing Tables Section 7-47-4-5 Connecting to the PLCConnect the Programming Device to a PLC in the network to transfer the rout-ing tables

Página 187

244Setting Routing Tables Section 7-47-4-8 Example Routing Table SettingsThis section shows examples of routing table settings.Example 1 The example b

Página 188 - Message Service

245Setting Routing Tables Section 7-4Example 3 The network structure example in the figure below shows routing tables for allnodes.Routing Tables on P

Página 189 - Introduction Section 6-1

246Setting Routing Tables Section 7-4Routing Tables on PLC 5Routing Tables on PLC 6Routing Tables on PLC 712010 02000312020 0133030 020 003Relay Netwo

Página 190 - "n" number

4Overview Section 1-1Maximum 62-node ConfigurationThe following Controller Link Units/Support Boards must be used to constructa network with more than

Página 191 - "m" num

247SECTION 8Communications TimingThis section explains details on Controller Link Network communications. Refer to this section for networkcommunicati

Página 192 - Boards for PCI Bus only.)

248Communications Mechanism Section 8-18-1 Communications Mechanism8-1-1 Data Transmissions over the NetworkIn a Controller Link Network, token passin

Página 193 - 1514131211 87

249Communications Mechanism Section 8-1Polling Node Each Controller Link Network always has a Unit that controls communicationswithin the network. Thi

Página 194

250Communications Mechanism Section 8-1If the node is always to be connected as a polled node when the power isturned on, set it as a polled node. If

Página 195

251Communications Cycle Time Section 8-28-1-4 Specifying Network ParametersThe network parameters can be specified from the Controller Link SupportSof

Página 196 - "n" number

252Communications Cycle Time Section 8-2E: Total number of bytes in messages transmitted during the communications cycleThe number of bytes in each me

Página 197

253Data Link I/O Response Time Section 8-3The number of bytes in each message differs according to the instructionbeing issued.Calculation Example Com

Página 198 - Support Boards for PCI

254Data Link I/O Response Time Section 8-3CVM1 and CV-series PLCs Under Asynchronous OperationWhen a CVM1 or CV-series CPU Unit is operating in asynch

Página 199 - 1514131211 87 0

255Data Link I/O Response Time Section 8-3Note 1. Use the above equations only if only one Controller Link Unit is mountedon the PLC. If other CPU Bus

Página 200

256Data Link I/O Response Time Section 8-3CVM1, CV-series, CS/CJ-series PLCs Under Synchronous Operation or C200HX/HG/HE and CQM1H-series PLCs Maximum

Página 201

5Overview Section 1-1Token Bus ModeConnecting Repeater Units Using GI Optical Fiber CableCS-series and CVM1/CV-series PLCs only.Token Ring ModeToken B

Página 202

257Data Link I/O Response Time Section 8-3The equation for maximum data link I/O response time is as follows:Note If the total number of data link wor

Página 203

258Data Link I/O Response Time Section 8-3There are three points shown in the diagram above where processing isdelayed, increasing the data link I/O r

Página 204

259Data Link I/O Response Time Section 8-3mum number of words (1,200 words) per time.For example, if the total number of data link words is 5,000, the

Página 205

260Data Link I/O Response Time Section 8-33. At node #7, data from the previous data exchange is still being transferred,causing a delay of up to one

Página 206

261Data Link I/O Response Time Section 8-3Case 4The following diagram illustrates the data flow that will produce the maximumdata link I/O response ti

Página 207 - 6-1-3 Send/Receive Data Areas

262Data Link I/O Response Time Section 8-3The equation for maximum data link I/O response time is as follows:Note If the total number of data link wor

Página 208

263Data Link I/O Response Time Section 8-3The equation for minimum data link I/O response time is as follows:Note If the total number of data link wor

Página 209 - Area Range

264Data Link I/O Response Time Section 8-32. Data exchange occurs just after the PLC at node #1 passes the token thatmakes it the polling node, causin

Página 210

265Message Delay Times Section 8-4In this case, the data processing time required for data exchange and the datatransmission time are not negligible a

Página 211

266Message Delay Times Section 8-4Note Be sure to take into account the time required for data links and program exe-cution, which are not included in

Página 212 - 6-3 Using the Message Service

6Overview Section 1-1Data LinksData links allow the constant sharing of data in predetermined data areasbetween nodes, between PLCs, or between a PLC

Página 213 - Network Status

267Message Delay Times Section 8-4Reception ProcessingNumber of words transferred × 0.00075 + 1.3 msNote The I/O response time can increase due to noi

Página 214 - SEND/RECV Flag Operations

268Message Delay Times Section 8-4Max. transmission delay = Link servicing interval (source node) + Link serviceprocessing (source node) + Transmissio

Página 215

269Message Delay Times Section 8-4Reception ProcessingCommands: 1.3 msResponses: Number of words transferred × 0.00075 ms + 2 msThe I/O response time

Página 216 - Instruction 2

270Message Delay Times Section 8-48-4-2 C200HX/HG/HE and CQM1H-series PLCsSEND(90) The following diagram indicates the data flow which will yield the

Página 217 - PLC Programming Examples

271Message Delay Times Section 8-4ExampleIn this example, the maximum transmission delay is calculated for an instruc-tion sending 256 words of data i

Página 218

272Message Delay Times Section 8-4interval (destination node) + Transmission processing (response) + Communi-cations cycle + Transmission delay (respo

Página 219 - C200HX/HG/HE PLCs

273Message Delay Times Section 8-4Note This communications cycle time is calculated assuming that there is no nodethat transmits event frames before t

Página 220 - Execution

274Message Delay Times Section 8-4

Página 221 - I/O Units

275SECTION 9Troubleshooting and MaintenanceThis section provides information on troubleshooting errors that occur during Controller Link Unit operatio

Página 222

276Troubleshooting Using Indicators Section 9-19-1 Troubleshooting Using IndicatorsThis section describes the errors indicated by the Controller Link

Página 224 - 6-5-3 DATA LINK STOP

7Overview Section 1-1SEND/RECV The SEND or RECV instruction sends or receives data in an area of a particu-lar node.The SEND instruction sends data fr

Página 225 - 6-5-4 CONTROLLER DATA READ

277Troubleshooting Using Indicators Section 9-1Not lit Not lit Not lit Not lit Power is not being sup-plied correctly to the PLC.Check the power suppl

Página 226 - 6-5-5 CONTROLLER STATUS READ

278Troubleshooting Using Indicators Section 9-1Lit --- --- Not lit Terminating resistance is not set correctly. (Wired Unit)Turn ON the terminating re

Página 227 - 6 5 4 3 2 1 0

279Troubleshooting Using Indicators Section 9-1Troubleshooting with LNK and M/A IndicatorsData Link Cannot be StartedThe following table describes the

Página 228 - 6-5-6 NETWORK STATUS READ

280Troubleshooting Using Indicators Section 9-1Node Cannot Participate in Data LinkThe following table describes the LNK and M/A indicators when a nod

Página 229

281Troubleshooting Using Indicators Section 9-1Configuring a Network with 33 Nodes or MoreProblem Status Cause and remedyThe node is not present in th

Página 230 - 6-5-7 DATA LINK STATUS READ

282Troubleshooting Using Indicators Section 9-1The data link status is showing statuses of 32 nodes only.The data link status storage area is set to d

Página 231 - 76543210

283Troubleshooting Using Indicators Section 9-1Configuring a Network with 32 Nodes or Less9-1-2 C200HX/HG/HE and CQM1H-series Controller Link UnitsTro

Página 232 - 6-5-8 ECHOBACK TEST

284Troubleshooting Using Indicators Section 9-1Not lit Not lit Not lit Not lit Power is not being sup-plied correctly to the PLC.Check the power suppl

Página 233 - 6-5-11 ERROR LOG READ

285Troubleshooting Using Indicators Section 9-1Troubleshooting with LNK and M/A IndicatorsData Link Cannot be StartedThe following table describes the

Página 234 - 6-5-12 ERROR LOG CLEAR

286Troubleshooting Using Indicators Section 9-1Node Cannot Participate in Data LinkThe following table describes the LNK and M/A indicators when a nod

Página 235 - CQM1H-series PLCs

8Overview Section 1-11-1-2 FeaturesThe Controller Link Network has the following features to meet the variousrequirements of FA sites.Data LinksFlexib

Página 236

287Troubleshooting Using Indicators Section 9-1Data Link Cannot be StoppedStopping the data link depends on the Controller Link Unit operating normall

Página 237 - 6-6-3 MEMORY AREA READ

288Troubleshooting Using Indicators Section 9-1• Setting hardware switches.Indicators Probable cause Probable remedyRUN ERC ERH INSLit Not lit Not lit

Página 238 - 6-6-4 MEMORY AREA WRITE

289Troubleshooting Using Indicators Section 9-1Indicators Probable cause Probable remedyRUN ERC ERH INSLit --- --- Not lit Terminating resistance is n

Página 239 - 6-6-6 PROGRAM AREA READ

290Troubleshooting Using Indicators Section 9-1Troubleshooting with LNK and M/A IndicatorsData Link Cannot be StartedThe following table describes the

Página 240 - 6-6-7 PROGRAM AREA WRITE

291Troubleshooting Using Indicators Section 9-1Node Cannot Participate in Data LinkThe following table describes the LNK and M/A indicators when a nod

Página 241 - 6-6-9 STOP

292Status Area and Troubleshooting Section 9-2Troubleshooting with the PWR IndicatorTroubleshooting with the T/R1 and T/R2 Indicators9-2 Status Area a

Página 242 - 6-6-10 CONTROLLER DATA READ

293Status Area and Troubleshooting Section 9-29-2-1 CS/CJ-series Controller Link UnitsThe status of the Unit and Network is indicated in the following

Página 243 - 0 0 0 0 0 0 0 0 0 0

294Status Area and Troubleshooting Section 9-2Note Data link status is valid only when the local node is participating in the datalink. Confirm that t

Página 244 - 6-6-13 CLOCK WRITE

295Status Area and Troubleshooting Section 9-24-Bit Format SpecifiedThe data link status can be reflected in 4-bit format only when using a CS1W-CLK21

Página 245 - 6-6-15 FORCED SET/RESET

296Status Area and Troubleshooting Section 9-2Communications error is 1: ONThe relevant node is not in the Network.Enter the node in the Net-work.A co

Página 246

9Overview Section 1-1Compatible with Different Node ConfigurationsThe following Controller Link Units are available for communications betweendifferen

Página 247

297Status Area and Troubleshooting Section 9-2Other StatusBit status Probable cause Probable remedyError log exists (CIO 1500 + 25 × n, bit 15) is 1:

Página 248 - 6-7 Response Codes

298Status Area and Troubleshooting Section 9-2Terminating Resistance Status: CIO 1500 + 25 × (Unit No.) + 24Data link table error (CIO 1500 + 25 × n,

Página 249 - 6-7-2 Network Relay Errors

299Status Area and Troubleshooting Section 9-29-2-2 C200HX/HG/HE Controller Link UnitsThe status of the Unit and Network is indicated in the following

Página 250 - Response Codes Section 6-7

300Status Area and Troubleshooting Section 9-2Polling Node Address, Startup Node Address: SR 238, SR 242Data Link Status: SR 239 to SR 241, SR 243 to

Página 251

301Status Area and Troubleshooting Section 9-2Data Link Status: First Data Link Status Word + 0 to + 15Note Refer to 5-4 Checking Data Link Status for

Página 252

302Status Area and Troubleshooting Section 9-2Data link participation is 0: OFFThe relevant node is not part of data links.Enter the relevant node in

Página 253

303Status Area and Troubleshooting Section 9-2Other StatusBit status Probable cause Probable remedyDuplicate Operating Lev-els/Refresh Error: Operatin

Página 254

304Status Area and Troubleshooting Section 9-29-2-3 CVM1 and CV-series Controller Link UnitsThe status of the Unit and Network is indicated in the fol

Página 255

305Status Area and Troubleshooting Section 9-2Data Link Status: CIO 1500 + 25 × (Unit No.) + 7 to + 22When the first data link status word is set to t

Página 256 - Network Interconnections

306Status Area and Troubleshooting Section 9-2Communications error is 1: ONThe relevant node is not in the Network.Enter the node in the Net-work.A co

Página 257

10Overview Section 1-1• If Repeater Units are installed at likely future branch points in the networkin advance, new nodes can be added by simply conn

Página 258

307Status Area and Troubleshooting Section 9-2Other StatusBit status Probable cause Probable remedyError log exists (CIO 1500 + 25 × n, bit 15) is 1:

Página 259 - 7-2-1 Local Networks

308Status Area and Troubleshooting Section 9-29-2-4 CQM1H-series Controller Link UnitsStatus AreaError Information: IR 190Data link table error (CIO 1

Página 260 - CX-Programmer

309Status Area and Troubleshooting Section 9-2Polling Node Address, Startup Node Address: IR 191Network Participation Status: IR 192 and IR 193Local D

Página 261 - 7-2-3 Other Remote Networks

310Status Area and Troubleshooting Section 9-2Bit Status and Error ProcessingData Link StatusBit status Probable cause Probable remedyPLC’s CPU Unit e

Página 262 - Local network

311Status Area and Troubleshooting Section 9-2Other StatusReceive area insufficient (short) is 1: ONThe send area at the rele-vant node is larger than

Página 263

312Status Area and Troubleshooting Section 9-2Terminating Resistance Status: IR 95Routing table error (IR 19002) is 1: ONThe routing table data within

Página 264 - Repeat the editing and

313Error Log Section 9-39-3 Error LogThe error log records errors that occur in the Controller Link Unit and the timethey occur. The error log can be

Página 265 - 7-4-4 Saving Routing Tables

314Error Log Section 9-3Time InformationThe time is recorded in BCD with one byte each for the year (the rightmosttwo digits), month, day, hour, secon

Página 266 - 7-4-5 Connecting to the PLC

315Error Log Section 9-3000E HexI/O Bus error 00 Hex 00 Hex Check the operating environment.Ye s C S / C J000F HexPLC initialization error Check the o

Página 267 - CS1-series PCs

316Error Log Section 9-30101 HexTransmission failed; local node not in NetworkCommand block Bits 0 to 7:Source node addressBits 8 to 14: Source Networ

Página 268

11Specifications and Configurations Section 1-2MethodAllocation addresses and sizes are all specified using the Automatic Data LinkCreation Parameters

Página 269 - Routing Tables on PLC 7

317Error Log Section 9-30109 HexTransmission failed; destination busyCommand block Bits 0 to 7:Source node addressBits 8 to 14: Source Network address

Página 270 - Communications Timing

318Error Log Section 9-30117 HexInternal buffer full Command block Bits 0 to 7:Source node addressBits 8 to 14: Source Network addressBit 15: OFFRespo

Página 271 - 8-1 Communications Mechanism

319Error Log Section 9-3Note 1. Applicable PLCs: CV = CVM1 and CV-series PLCs, CS/CJ = CS-seriesand CJ-series PLCs, All = All models of PLC.2. Errors

Página 272 - Operating level 0

320Troubleshooting Error Messages in CX-Net Data Link Table Check Section 9-4Error StatusThe status of each bit indicates that an error has occurred a

Página 273 - 8-1-3 Network Parameters

321Troubleshooting Error Messages in CX-Net Data Link Table Check Section 9-4Example Display of Error ListNote (1) If any errors (except for warnings)

Página 274 - 8-2 Communications Cycle Time

322Troubleshooting Error Messages in CX-Net Data Link Table Check Section 9-4The XX symbol refers to the corresponding node address. The twoasterisks

Página 275 - 8-2-2 Inactive Data Links

323Cleaning and Inspection Section 9-59-5 Cleaning and InspectionThis section describes cleaning and inspection procedures that are to be per-formed a

Página 276 - 8-3-1 Data Exchange Timing

324Handling Precautions Section 9-69-6 Handling PrecautionsThe Controller Link Unit is a Network device. If the Unit is damaged, it willeffect the ent

Página 277 - 8-3-2 Data Processing Time

325Handling Precautions Section 9-6Relay Terminal Blocks (CJ1W-TB101) can be used on any node but theend nodes to enable replacing the Controller Link

Página 278 - 8-3-3 Calculation Example

326Handling Precautions Section 9-6CVM1 and CV-series Controller Link UnitsCQM1H-series Controller Link Units2. Turn the power off once, connect the C

Página 279 - HE and CQM1H-series PLCs

12Specifications and Configurations Section 1-2Connecting Repeater Units Using Twisted-pair Cable in Wired SystemsT-Branch WiringLong-distance Wiring

Página 280

327Handling Precautions Section 9-6Using the above procedure to reset the network parameters of the node thatwas replaced to the same as the other nod

Página 281

328Handling Precautions Section 9-62. Detach the communications cables and the Bus Connection Unit attachedto the Controller Link Unit to be replaced

Página 282

329Handling Precautions Section 9-6previous status. If, however, the CPU Unit is replaced, the data link tables androuting tables will need to be rese

Página 283

330Handling Precautions Section 9-6

Página 284

331SECTION 10Adding Nodes and Editing Active Data Link TablesThis section describes the methods used to perform functions without turning OFF the PLC

Página 285

332Adding Nodes Using a Repeater Unit Section 10-110-1 Adding Nodes Using a Repeater Unit10-1-1 OverviewThe CS1W-RPT01 Repeater Unit can be used to ad

Página 286 - Output ON delay

333Adding Nodes Using a Repeater Unit Section 10-110-1-2 Procedure for Adding Nodes10-1-3 Precautions when Connecting Nodes Using a Repeater UnitWhen

Página 287 - ◆ Program

334Adding Nodes Using a Repeater Unit Section 10-1• If automatic settings are used, make sure that the appropriate DM Areaparameters have been set.Che

Página 288 - 8-4 Message Delay Times

335Adding Nodes Using a Repeater Unit Section 10-1Before connecting the new nodes to the existing network, always set the poll-ing/polled node setting

Página 289 - × 0.00075 ms + 2 ms

336Changing the Data Link Tables with Active Data Links Section 10-210-2 Changing the Data Link Tables with Active Data Links 10-2-1 OverviewThe data

Página 290 - × 0.00075 + 1.3 ms

13Specifications and Configurations Section 1-2Converting Part of the Transmission Line to Optical FiberTwo Repeater Units of the same model must be u

Página 291

337Changing the Data Link Tables with Active Data Links Section 10-2Data link communications will continue, so the Communications Error Flag forthe da

Página 292

338Changing the Data Link Tables with Active Data Links Section 10-210-2-5 Procedure for Changing the Data Link Tables with CX-ProgrammerThe procedure

Página 293 - × 0.00125 ms + 2.3 ms

339Changing the Data Link Tables with Active Data Links Section 10-26. Use the mouse to select node 1, whose data link table is to be changed. 7. Sele

Página 294

340Changing the Data Link Tables with Active Data Links Section 10-210. The Data Link Table Transfer Confirmation Message Box will be displayed.Click

Página 295

341Changing the Data Link Tables with Active Data Links Section 10-2

Página 296

342Changing the Data Link Tables with Active Data Links Section 10-2

Página 297

343Appendix AStandard ModelsController Link UnitsController Link Support BoardController Link Support SoftwareRepeater UnitsCommunications Cables (Twi

Página 298 - SECTION 9

344Standard Models Appendix ACX-Programmer with CX-NetCPU Units and Programming DevicesCPU UnitsApplicable computerName Model number Applicable PLCsIB

Página 299 - CJ-series Unit

345Standard Models Appendix AOther Products Used with Controller Link UnitsRefer to the operation manual for the relevant PLC for further information

Página 301

14Specifications and Configurations Section 1-21-2-3 Communications SpecificationsWired SystemNote 1. The maximum distance between nodes depends on th

Página 302

347Appendix BMemory AreasThis appendix provides easy reference to the words in PLC memory areas used by Controller Link Networks.CS/CJ-series PLCsAuxi

Página 303

348Memory Areas Appendix BCS/CJ CPU Bus Unit Duplication Error FlagBit A40113 is turned ON when two CS/CJ CPU Bus Units have been assigned the same un

Página 304

349Memory Areas Appendix BNetwork Participation Status: CIO 1500 + 25 × (Unit No.) + 2, + 3 (See pages 190, 304.)Local Data Link Participation Status:

Página 305

350Memory Areas Appendix B4-Bit Format SpecifiedTerminating Resistance Status (CIO 1500 + 25 × (Unit No.) + 24 (See page 305.)Node 4PLC status0: Ina

Página 306

351Memory Areas Appendix BDM Area: CS/CJ CPU Bus Unit AreaThe CS/CJ CPU Bus Unit Area (DM Area) is allocated to CS/CJ CPU Bus Units according to the u

Página 307

352Memory Areas Appendix BParameters for Automatically Setting Data Links with Equality Layout: D30000 + 100 × (Unit No.) + 1 to 9 (See page 145.)Para

Página 308

353Memory Areas Appendix B1 to 1 TypeWords N+22 through N+25 register nodes that will participate in the data links. The numbers shown in the tableare

Página 309

354Memory Areas Appendix BWords N+22 through N+25 register nodes that will participate in the data links. The numbers shown in the tableare the node a

Página 310 - M/A: Data link mode

355Memory Areas Appendix BOperating Level Status: SR 252 (See pages 189, 300.)AR AreaDuplicate Operating Levels/Refresh Error: AR 00 (See page 299.)Ro

Página 311 - • Setting hardware switches

356Memory Areas Appendix BCommunications Controller Hardware Error, EEPROM Error: AR 11, AR 15 (See page 299.)Service Time: AR 16, AR 17 (See page 299

Página 312

15Specifications and Configurations Section 1-2Communications Specifications when Using the CS1W-RPT01 Repeater Unit in a Wired NetworkNote 1. Specifi

Página 313

357Memory Areas Appendix BRouting Tables (DM 6450 to DM 6499) (See page 243.)When the use of routing tables is enabled by the software switch setting,

Página 314 - 9-1-4 Repeater Units

358Memory Areas Appendix BCPU Bus Unit NumbersBits A41000 through A41015 correspond to CPU Bus Units #0 through #15, respectively. When two CPU BusUni

Página 315

359Memory Areas Appendix BLocal Data Link Participation Status: CIO 1500 + 25 × (Unit No.) + 6 (See page 304.)Data Link Status: CIO 1500 + 25 × (Unit

Página 316 - Status Area

360Memory Areas Appendix BDM Area: CPU Bus Unit AreaThe CPU Bus Unit Area (DM Area) is allocated to CPU Bus Units according to the unit numbers assign

Página 317 - × (Unit No.) + 7 to + 22

361Memory Areas Appendix BParameters for Automatically Setting Data Links: DM 2000 + 100 × (Unit No.) + 1 to + 9 (See page 147.)CQM1H-series PLCsAR Ar

Página 318 - × (Unit No.) (+ 7 to +22))

362Memory Areas Appendix BCommunications Unit Flags, Control Bits, and Status InformationLocal Data Link Participation Status: IR 90 (See page 309.)Da

Página 319

363Memory Areas Appendix BController Link Status InformationError Information: IR 190 (See page 309.)Polling Node Address, Startup Node Address: IR 19

Página 320 - Other Status

364Memory Areas Appendix BAutomatic Data Link Parameters: DM 6401 to DM 6409 (See page 150.)Routing Tables: DM 6450 to DM 6499 (See page 239.)These wo

Página 321 - × (Unit No.) + 24

365Appendix CUsing the Relay Terminal BlockThis appendix describes how to use the CJ1W-TB101 Wired Controller Link Unit Relay Terminal Block. Using aR

Página 322

366Using the Relay Terminal Block Appendix C4. Attach the terminal block cover to the communications terminal block on the Controller Link Unit.Replac

Página 323

16Specifications and Configurations Section 1-21-2-4 Controller Link Unit Models and PLCsWired SystemThere are five Controller Link Units: One for CVM

Página 324 - Data Link Status

367Using the Relay Terminal Block Appendix CNote 1. Signal will still be flowing through the communications cables during the replacement procedure i

Página 326

369IndexNumerics1 to 1 type, 10, 130, 1391:N allocations1 to 1 type, 10, 130, 139chain type, 10, 130, 141common type, 10, 130, 1354-bit format, 156, 1

Página 327

370Indexsettings, 93CJ Seriessettings, 89CJ-series PLCs, 46CQM1H Seriessettings, 100CQM1H-series PLCs, 53CS Seriessettings, 86CS-series PLCs, 44CVM1 a

Página 328

Index371error log, 7reading, 210response codes, 227FAL/FALS No., 221fatal error data, 220FINS commandserrors, 227response codeserrors, 227sending and

Página 329

372Indexreading, 219reading controller status, 203, 220receiving routing table settings, 243status, 219polling cycledefinition, 248polling nodesetting

Página 330

Index373changing PV, 215reading Completion Flag status, 214, 216reading PV, 216troubleshooting, 276status area, 292status flags, 301using indicators,

Página 331

374Index

Página 332

375Revision HistoryA manual revision code appears as a suffix to the catalog number on the front cover of the manual. The following table outlines the

Página 333

376Revision History06 February 2003 “PC” changed to “PLC” throughout the manual. Information related to the CQM1H-CLK21 was added and information rela

Página 334

vNotice:OMRON products are manufactured for use according to proper procedures by a qualified operatorand only for the purposes described in this manu

Página 335 - 1: ON

17Specifications and Configurations Section 1-2Note A Controller Link Support Board can be installed into an IBM PC/AT or com-patible computer to conn

Página 336 - 9-3 Error Log

OMRON CorporationControl Devices Division H.Q.Shiokoji Horikawa, Shimogyo-ku,Kyoto, 600-8530 JapanTel: (81)75-344-7109/Fax: (81)75-344-7149Regional He

Página 337 - 9-3-2 Error Codes

Authorized Distributor:Cat. No. W309-E1-09 Note: Specifications subject to change without noticePrinted in JapanThis manual is printed on 100% recycle

Página 338 - Error Log Section 9-3

18Specifications and Configurations Section 1-2CS/CJ-series Controller Link Unit ModelsNote A network can contain both nodes with maximum of 20,000 da

Página 339

19Specifications and Configurations Section 1-21-2-5 Devices for ConnectionTo set up a Controller Link Network, the following devices are needed in ad

Página 340

20Specifications and Configurations Section 1-2Note 1. Repeater Units do not use a node address.2. See Connection Procedure for an explanation of how

Página 341

21Specifications and Configurations Section 1-2Note Normally, the communications cable must be disconnected from a Wired Con-troller Link Unit to repl

Página 342

22Specifications and Configurations Section 1-22. For automatic data link creation with 1:N allocations or when changingdata link tables while the dat

Página 343 - Table Check

23Specifications and Configurations Section 1-2Using a Computer Node A computer that is a node on the Network can also be used to control theControlle

Página 344

24Specifications and Configurations Section 1-2Controller Link Support Software Menu OverviewNote 1. Refer to the Controller Link Support Software Ope

Página 345

25Selection of Communications Functions Section 1-3When Operating on Personal Computer as Peripheral SoftwareWhen Operating on Personal Computer Conne

Página 346 - 9-5 Cleaning and Inspection

26Basic Procedures Section 1-4other PLCs in other nodes or from one PLC to IBM PC/AT or compatible com-puters.1-4 Basic ProceduresPreparations C200HX/

Página 347 - 9-6 Handling Precautions

viUnit Versions of CS/CJ-series Controller Link UnitsUnit VersionsA “unit version” has been introduced to manage CS/CJ-series Controller Link Units ac

Página 348 - Resetting Network Parameters

27Application Precautions Section 1-5b) This setting is valid only with the CS1W-CLK21-V1 and CS1W-CLK21-V1. Reset the power to the PLC after setting.

Página 349

28Application Precautions Section 1-5• Set routing tables at all the nodes in all the networks when multiple net-works are connected.• When using the

Página 350 - 9-6-3 Replacing the Unit

29Application Precautions Section 1-5• The Wired Network 62 Node Enable Bit in the DM Parameter Area soft-ware switches of CS1W-CLK21-V1 and CJ1W-CLK2

Página 351

30Application Precautions Section 1-5

Página 352

31SECTION 2Basic ProceduresThis section describes the basic procedures to use the Controller Link Unit. The settings necessary for using each of thefu

Página 353

32Data Links Procedures Section 2-12-1 Data Links Procedures2-1-1 Manually Setting Data LinksWhen the data link mode is set for manual data link table

Página 354 - SECTION 10

33Data Links Procedures Section 2-16. Set the data link mode.Note a) When using fewer than 33 nodes, make sure that the Wired Net-work 62 Node Enable

Página 355 - 10-1-1 Overview

34Data Links Procedures Section 2-18. Start the data links.Note a) Data link Start/Stop Bit (N= unit number):CS/CJ Series: Word 0 of DM30000 + 100 × N

Página 356

35Data Links Procedures Section 2-12. Prepare for communications.3. Turn ON the power to the PLC.4. Connect the Programming Device.5. Create I/O table

Página 357

36Data Links Procedures Section 2-1Note a) When using fewer than 33 nodes, make sure that the Wired Net-work 62 Node Enable Bit if the DM Parameter Ar

Página 358 - 10-1-2 Procedure for Adding

viiUsing the Unit Version LabelsUnit version labels are provided with the product. These labels can be attached to the front of previousController Lin

Página 359 - 10-2-1 Overview

37Data Links Procedures Section 2-1• 1:N allocation (Compatible with CS1W-CLK21-V1 and CJ1W-CLK21-V1)Common TypeNote For automatic data link creation

Página 360 - Links (Theoretical)

38Data Links Procedures Section 2-11 to 1 TypeNote For automatic data link creation with 1:N allocation, use CX-Net inCX-Programmer version 3.2 or hig

Página 361 - Programmer

39Data Links Procedures Section 2-1Chain TypeNote For automatic data link creation with 1:N allocations, use the CX-Netin CX-Programmer version 3.2 or

Página 362

40Message Service Procedure Section 2-2C200HX/HG/HE: AR 0700 (operating level #0), AR 0704 (operating level #1)CVM1/CV Series: Word 0 of DM 2000 + 10

Página 363

41Message Service Procedure Section 2-26. Set the data link mode.Note When using fewer than 33 nodes, make sure that the Wired Network62 Node Enable B

Página 364

42Message Service Procedure Section 2-2

Página 365

43SECTION 3Installation and WiringThis section describes how to install a Controller Link Unit and how to wire the Controller Link Network.3-1 Compone

Página 366 - Appendix A

44Component Names and Functions Section 3-13-1 Component Names and FunctionsThis section describes the names and functions of the Controller Link Unit

Página 367 - CX-Programmer with CX-Net

45Component Names and Functions Section 3-1Wired Unit IndicatorsNote Even when the local node does not participate in the data link, theindicator will

Página 368 - Standard Models Appendix A

46Component Names and Functions Section 3-1Dimensions (Unit: mm)3-1-2 CJ-series Controller Link Units10135130CLK21-V1UNIT No.RUNCLK21-V1ERC INSERH M/A

Página 370 - Appendix B

47Component Names and Functions Section 3-1Wired Unit IndicatorsNote Even when the local node does not participate in the data link, the M/A indicator

Página 371 - × (Unit No.) (See page 304.)

48Component Names and Functions Section 3-1Dimensions (Unit: mm)6531UNIT No.RUNCLK21-V1ERC INSERH M/A LNK RD90 2.72.7NODE No.x101x1000123456789ABCDEF0

Página 372 - Memory Areas Appendix B

49Component Names and Functions Section 3-13-1-3 C200HX/HG/HE Controller Link UnitWired Unit Indicators1Indicators LED indicators that display the Uni

Página 373

50Component Names and Functions Section 3-1Note Even when the local node does not participate in the data link, theindicator will be lit if there are

Página 374

51Component Names and Functions Section 3-13-1-4 CVM1 and CV-series Controller Link UnitWired Unit IndicatorsUnit number switches Two rotary switches.

Página 375 - × (Unit No.) +

52Component Names and Functions Section 3-1Note Even when the local node does not participate in the data link, theindicator will be lit if there are

Página 376

53Component Names and Functions Section 3-13-1-5 CQM1H-series Controller Link UnitWired Unit IndicatorsIndicators LED indicators that display the Unit

Página 377

54Component Names and Functions Section 3-1Note Even when the local node does not participate in the data link, theindicator will be lit if there are

Página 378

55Component Names and Functions Section 3-1Repeater Unit IndicatorsDimensions (Unit: mm)Name Color Status MeaningPWR(Power supply)Green Lit Power supp

Página 379

56Component Names and Functions Section 3-13-1-7 Wire-to-Optical (H-PCF) Repeater Unit Repeater Unit IndicatorsON12ON12DC24VINPUTSL1SL2T/R2T/R1PWRCS1W

Página 380

ixTABLE OF CONTENTSPRECAUTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xix1 Intended Audience . . . . . . . . . . . . .

Página 381 - CIO Area: CPU Bus Unit Area

57Component Names and Functions Section 3-1Dimensions (Unit: mm)3-1-8 Wire-to-Optical (GI) Repeater Unit 75.673.3859Two, 4.5 dia.30902181(Unit: mm)ON1

Página 382

58Unit Installation Section 3-2Repeater Unit IndicatorsDimensions (Unit: mm)3-2 Unit Installation• The Controller Link Unit is mounted onto a CPU Back

Página 383 - DM Area: CPU Bus Unit Area

59Unit Installation Section 3-22. Be sure that all screws on the Backplane, the Bus Connection Unit, the ter-minal block, and cables are tightened fir

Página 384

60Unit Installation Section 3-2Installing with Another Communications UnitWhen installing a Controller Link Unit along with another CommunicationsUnit

Página 385

61Unit Installation Section 3-2CS-series PLCsUp to a total of eight Controller Link Units with unit version 1.2 or later (wired,optical, and optical r

Página 386

62Unit Installation Section 3-2Note When installing several CS-series CPU Bus Units at the same time, a total of16 CS-series CPU Bus Units maximum may

Página 387

63Unit Installation Section 3-2CJ-series PLCsUp to a total of four Controller Link Units for CJ-series PLCs can be connectedin a CPU Rack or a Expansi

Página 388 - Appendix C

64Unit Installation Section 3-2Example: Using the C200HW-PA204 Power Supply Unit supplying a maxi-mum current of 4.6 A (5 V) and maximum power of 30 W

Página 389 - 9-6-1 Replacing

65Unit Installation Section 3-2Screw-mounting a Repeater UnitUse M4 × 15 screws to mount the Unit as shown in the following diagram.Mounting a Repeate

Página 390

66Wiring Section 3-3End Plate: PFP-M (2 Plates required per Repeater Unit)3-3 Wiring3-3-1 Communications CablesUsing the specified twisted-pair cable,

Página 391

xTABLE OF CONTENTSSECTION 5Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1055-1 What Are Data Links? . .

Página 392 - Numerics

67Wiring Section 3-33. Do not connect the shield cable of the communications cable to a groundthat is also being used for power-system devices, such a

Página 393

68Wiring Section 3-3Using a Relay Terminal BlockNote 1. Mounting and dismounting during communications is not possible for Re-lay Terminal Blocks conn

Página 394

69Wiring Section 3-35. Twist firmly the portion of the signal lines that are exposed.6. Apply vinyl tape or heat-shrinking tube to the end of the cove

Página 395

70Wiring Section 3-3b) The approximate dimension for when the cable has been wiredfrom the terminal block along the front of the Unit is shown in thef

Página 396

71Wiring Section 3-310. When bending a communications cable, allow 60 mm or more for the bend-ing radius (R).11. Do not place any object on the commun

Página 397

72Wiring Section 3-38. Do not place any object on the power cable.9. Check that connectors are correctly attached before using the Unit.Power Supply S

Página 398 - Revision History

73Wiring Section 3-35. Move the cable connector so that the loose ends are on the left-hand side,and insert the Unit’s optical connector as far as it

Página 399

74Wiring Section 3-3Communications CablesOptical Bus or Optical Ring System (H-PCF Cable)The following devices are required for the Optical Bus or Opt

Página 400

75Wiring Section 3-3Optical Fiber Cables with Connectors (Indoor Use Only)The following Optical Fiber Cables are available with Connectors alreadyatta

Página 401 - Printed in Japan

76Wiring Section 3-3CS1W-RPT03 (GI)Note 1. Always use the specified Optical Fiber Cables.2. Although the Optical Fiber Cables can be distinguished by

Comentários a estes Manuais

Sem comentários