325
Instruction
OFF execution time (
µs)ON execution time (µs)
Conditions
AND LD --- 0.375 0.375
OR LD --- 0.375 0.375
OUT For IR and SR 23600 to SR 25515 0.563 0.563
For SR 25600 to SR 51115 0.938 0.563
OUT NOT For IR and SR 23600 to SR 25515 0.563 0.563
For SR 25600 to SR 51115 0.938 0.563
TIM Constant for SV 1.125 R: 1.125
IL: 1.125
JMP: 1.125
:DM for SV R: 39.0875
IL: 1.125
JMP: 1.125
For designated words 256 to 511 R: 22.2875
IL: 1.125
JMP: 1.125
CNT Constant for SV 1.125 R: 1.125
IL: 1.125
JMP: 1.125
:DM for SV R: 39.0875
IL: 1.125
JMP: 1.125
For designated words 256 to 511 R: 22.0875
IL: 1.125
JMP: 1.125
SET For IR and SR 23600 to SR 25515 0.563 0.563
For SR 25600 to SR 51115 0.938 0.563
RSET For IR and SR 23600 to SR 25515 0.563 0.563
For SR 25600 to SR 51115 0.938 0.563
NOP(00) --- 0.375 ---
END(01) --- 34.20 ---
IL(02) --- 11.44 14.00
ILC(03) --- 12.60 12.64
JMP(04) --- 12.32 14.56
JME(05) --- 12.28 12.28
FAL(06) 01 to 99 --- 93.76 0.375
FAL(06) 00 --- 77.56 0.375
FALS(07) --- 4.28 ms 0.375
STEP(08) --- 50.60 (with operand) 2.25
24.56 (without operand)
SNXT(09) --- 13.96 2.25
Instruction Execution Times Section 6-3