Omron CPU Unit CJ2 Manual do Utilizador Página 33

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 40
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 32
33
Ordering Information
Analog Output Units
Unit
classification
Product
name
Output
points
Signal
range
selection
Signal
range
Resolution
Conversion
speed
Accu-
racy (at
ambient
temper-
ature of
25°C)
External
connection
External
power
supply
No. of
unit
numbers
allocated
Current
consumption
(A)
Model Standards
5 V 24 V
CJ
Special
I/O
Units
Analog
Putput
Units
8
outputs
Set
separately
for each
input
1 to
5 V,
0 5 to
5 V,
0 to 10
V,
−10 to
10 V
1/4,000
(Settable
to
1/8,000)
1 ms/ point
max.
(Settable to
250
μs/point)
±0.3% of
F.S.
Removable
terminal
block
24
VDC
+10%
–15%,
140 mA
max.
1
0.14
0.14
(See
note.)
CJ1W-
DA08V
UC1, N, L,
CE
8
outputs
4 to 20
mA
24
VDC
+10%
–15%,
170 mA
max.
0.14
0.17
(See
note.)
CJ1W-
DA08C
UC1, N,
CE
4
outputs
1 to
5 V,
0 to
5 V,
0 to 10
V,
−10 to
10 V,
4 to 20
mA
1/4000
1 ms/ point
max.
Voltage
output:
±0.3% of
F.S.
Current
output:
±0.5% of
F.S.
24
VDC
+10%
–15%,
200 mA
max.
0.12
0.2
(See
note.)
CJ1W-
DA041
UC1, N, L,
CE
2
outputs
24
VDC
+10%
–15%,
140 mA
max.
0.12
0.14
(See
note.)
CJ1W-
DA021
Note: This is for an external power supply, and not for internal current consumption
Analog I/O Units
Unit
classification
Product
name
No. of
points
Signal
range
selection
Signal
range
Resolution
(See note.)
Conversion
speed
(See note.)
Accuracy
(at ambient
temperature
of 25°C)
External
connection
No. of
unit
numbers
allocated
Current
consumption
(A)
Model Standards
5 V 24 V
CJ
Special
I/O
Units
Analog
I/O
Units
4 inputs
Set
separately
for each
input
1 to 5
V,
0 to 5
V,
0 to
10 V,
−10 to
10 V,
4 to
20
mA
1/4,000
(Settable
to
1/8,000)
1 ms/point
(Settable to
500 μs/
Voltage input:
±0.2% of F.S.
Current input:
±0.2% of F.S.
Removable
terminal
block
1 0.58
CJ1W-
MAD42
UC1, N, L,
CE
2
outputs
Voltage output:
±0.3% of F.S.
Current output:
±0.3% of F.S.
Note: The resolution and conversion speed cannot be set independently. If the resolution is set to 1/4,000, then the conversion speed will be 1 ms/point.
Vista de página 32