2 Instructions
2-38
CP1E CPU Unit Instructions Reference Manual(W483)
END
Applicable Program Areas
Flags
There are no flags affected by this instruction.
Function
END(001) completes the execution of a program for that cycle. No instructions written after END(001)
will be executed.
Precautions
Always place END(001) at the end of each program. A programming error will occur if there is not an
END(001) instruction in the program.
Instruction Mnemonic Variations
Function
code
Function
END END --- 001 Indicates the end of a program.
Symbol
END
Area Step program areas Subroutines Interrupt tasks
Usage Not allowed Not allowed OK
END(001)